Medium voltage | High voltage | Low voltage | Low voltage |
Air and oil insulated switch gear (HHB) |
Capacitor protection (HHD) Distribution transformers Voltage transformers (PT) |
D fuses: AC 400 V - AC 500 V / DC 250 V - DC 500 V Current rating: 0.5 A to 200 A Surface mount & thru hole for PC boards SMD 125V & 250V |
5 x 20 - 6.3 x 32 - 5 x 25 5 x 30 - 8 x 50 - 8 x 85 10 x 85 - 8 x 120 - 8 x 150 mm |
Semiconductor Fuses
Class | Voltage Rating | Current Rating | Standards | Product Reference |
aR | 660 to 1000VAC | 10 to 400A | DIN 43653; IEC 60269-4; DIN VDE 0636-40; UL 248-13 | |
gR/aR | 440 to 500VAC | 2 to 200A | DIN VDE 0636-40; DIN 49515/49360 | |
gR/aR | 660 to 5000VDC | 6 to 800A | IEC 60269-4; DIN VDE 0636-40;DIN 49515/49360 | |
aR | 240 to 700VAC | 5 to 900A | IEC 60269-4; BS 88-4 | |
aR/gR | 500 to 200VAC | 16 to 800A | DIN 43620; DIN 43653 | |
aR * | 700AC / 1300VAC | 50 to 1600A | DIN 43653; DIN VDE 0636-40;IEC 60269-4;UL 248-13 |
Class | Size |
Type |
Voltage rating |
Current Rating |
Standard |
Product Reference |
gRL | 00/1/2/3 | Knife blade contact fuses | 690VAC | 16 to 800A | DIN 43620 | URL |
Fuses with bolted contact | 690VAC | 16 to 800A | DIN43653 | |||
Cylindrical fuses | 500 to 690VAC | 6 to 100A | N/A |
Class |
Size |
Type |
Voltage rating |
Product Reference |
gR/aR/gRL | 5 x 20 mm | Cylindrical fuse | AC 250 V | URZ |
6.35 x 32 mm | AC 500 - 1000 V | |||
10 x 38 mm | AC 600 - 1000 V | |||
14 x 51 mm | AC 500/600V - 690/700 V | |||
22 x 58 mm | AC 500/600 V - 690/700 V | |||
27 x 60 mm | AC 660 V - 1000 V |
Fuses For Semiconductor Protection
- High interrupting rating 200 kA
- Very low I2t -values
- Voltage ratings AC 690/700 V and AC 1250/1300 V
- Suitable for North American and European standard
- Reliable also at high cyclic loading
- Fuse bases and other accessories for Fuse semiconductor protection are available
Class | Size |
Voltage rating |
Current Rating |
Standard |
Product Reference |
aR | 1/2/3/4 | AC 700 V / AC 1300 V | 50 up to 3000 A | DIN 43653 | URS |
DIN VDE 0636-40 | |||||
IEC 60269-4 | |||||
UL 248-13 |
Download PDF Catalog for more Information
Fuses For Semiconductor Protection European Standard Class gRL (gs)
- High current limitation
- Low power losses
- Semiconductor protection against short circuit faults
- Cable protection against overload current
- Low I2t -values
- High interrupting rating up to 200 kA
- Compliance with the following standards: IEC 60269-1 / -2-1 and -4 DIN
- Class gRL follows the requirements of the new standardized class gS
- Fuse bases and other accessories for Fuse semiconductor protection are available
Download PDF Catalog for more Information
Fuses For Semiconductor Protection Cylindrical Fuses - European Standard
- High interrupting rating up to 300 kA
- Voltage rating 250 up to 1000 V AC
- Protection of Power Semiconductors according to IEC 60269-1 and -4
- With or without integrated striker pin
- Class aR according to IEC 60269-4 and DIN VDE 0636-40
- Class gR according DIN VDE 0636-40
- Fuse-Bases / Fuse-Clips and Accessories are available
Class | Size |
Voltage rating |
Current Rating |
Standard |
Product Reference |
gR aR gRL | 5 x 20 mm | AC 250 V | 125 mA - 200 A | IEC 60269-1 and -4DIN VDE 0636-23UL 248-13 | URZ |
6.35 x 32 mm | AC 500 - 1000 V | ||||
10 x 38 mm | AC 600 - 1000 V | ||||
14 x 51 mm | AC 500/600V - 690/700 V | ||||
22 x 58 mm | AC 500/600 V - 690/700 V | ||||
27 x 60 mm | AC 660 V - 1000 V |
Download PDF Catalog for more Information
DC-Application / Traction Fuse
- Designed for heavy duty applications
- Shock and vibration proved
- Some types with additional microswitches
- Developed according customers specification
- Individual tested time constants
- Designed for long lasting live under severe service conditions
- OEM inquires for custom Traction Fuse are welcome
Class |
Voltage rating |
Current Rating |
Standard |
Product Reference |
gR aR gRL | DC 660 V - DC 5000 V | 6 A - 800 A | UIC 550 IEC 60269-4 DIN VDE 0636-23 | URDC |
Download PDF Catalog for more Information
Miniature Fuses G
- Very high interrupting rating up to 70 kA
- High ratings of voltages up to 10 kV
- Large range of current ratings available for semiconductor protection
- Fuse bases, clips and accessories are available
Class | Size |
Voltage rating |
Current Rating |
Standard |
Product Reference |
F fast acting T time lag TT very slow M medium time lag FF very fast acting |
Cylindrical fuses: 5 x 20 6.3 x 32 5 x 25 5 x 30 8 x 50 8 x 85 10 x 85 8 x 120 8 x 150 mm |
65 V - 10kV | 6 A - 800 A | IEC 60127 DIN VDE 0820 CEE4 UL 248-14, UL 512 CSA-C22.2 No. 248.14 | G |
Radial lead 2 pin fuses: KS, Ø 8.4 mm | 250 V | 40mA - 10A | |||
SMD fuses: Voltage ratings: 65 V - 10 kV | 125-250 V | 40mA - 15A |
Download PDF Catalog for more Information
Medium Voltage Fuses For Capacitors
Voltage rating |
Current Rating |
Standard |
Product Reference |
3.2/ 4.8 / 5.5 / 7.2 / 8.3 / 15.5 / 23kV | 6.3 - 500 A | IEC 60 282-1 IEC 60 549 | HHC |
Download PDF Catalog for more Information
High Voltage Fuses
The connection caps are fitted inside the silver plated copper end caps by spot welding. The copper end caps themselves are press-fitted onto the porcelain tube, which is glazed inside and outside. The end caps are furthermore mechanically fixed to the porcelain tube and additionally sealed by a durable elastimer sealing medium. This sealing method has been proven over many decades of positive field experience and ensures tightness against ingress of humidity. Inquires for fuse high voltage custom applications are welcome.
Download PDF Catalog for more Information
High Voltage Fuses
- Protection of Motor circuits according IEC 60644. High resistance against cyclic and peak current loads, avoiding ageing because of high motor start up currents
- Low power losses, minimizing temperature increase in narrow contactor enclosures
- Low minimum interrupting currents for operation of over-currents in the range 3 - 3.5 x rated current
- Availability of temperature limiters for switchgear protection against excessive temperature rise
- Type tested according IEC 60470 in cooperation with the major European Panel builders
- Available in DIN 43625 and BS 2692 dimensions
Class |
Voltage rating |
Current Rating |
Standards |
Product Reference |
Back up | AC 3.6 - 7.2 kV | 50 - 450 A | Dimensions: DIN 43625 and BS 2692Electrical: IEC 60644 IEC 60470 IEC 60282-1 BS 2692 | HHM |
Download PDF Catalog for more Information
Medium Voltage Fuses
Download PDF Catalog for more Information
Medium Voltage Fuses - British Standard
-
IEC 60282-1
-
BS 2692
-
ESI 12-8
Download PDF Catalog for more Information
Medium Voltage Fuses - French Standard
-
IEC 60282-1
-
NFC 64210
Download PDF Catalog for more Information
Medium Voltage Fuses - European Standard
Download PDF Catalog for more Information
Low Voltage Fuses - European NH Knife-Blade Fuse System
Operation class |
Application |
gG | General Purpose Cable and Line protection |
gB | For general application |
aM | Motor circuit short circuit protection |
gTr | General Purpose Transformer Protection |
gTF | For general application |
Download PDF Catalog for more Information
Fuses For Semiconductor Protection - European Standard
Download PDF Catalog for more Information
Fuses For Semiconductor Protection - European Standard
Download PDF Catalog for more Information
Knife Blade Contact Fuse - German Standard
Download PDF Catalog for more Information
Fuses For Semiconductor Protection - European-British Standard
Download PDF Catalog for more Information
D Fuses
Download PDF Catalog for more Information
Class |
Voltage rating |
Current Rating |
Standards |
Product Reference |
aR | 660 to 1000VAC | 10 to 400A | DIN 43653; IEC 60269-4; DIN VDE 0636-40; UL 248-13 | URB |
gR/aR | 440 to 500VAC | 2 to 200A | DIN VDE 0636-40; DIN 49515 / 49360 | URD |
gR/aR | 660 to 5000VDC | 6 to 800A | IEC 60269-4;DIN VDE 0636-40;DIN 49515/49360 | URDC |
aR | 240 to 700VAC | 5 to 900A | IEC 60269-4; BS 88-4 | URE |
aR/gR | 500 to 200VAC | 16 to 800A | DIN 43620; DIN 43653 | URM |
aR * | 700AC / 1300VAC | 50 to 1600A | DIN 43653; DIN VDE 0636-40;IEC 60269-4;UL 248-13 | URS |
Type |
Voltage rating |
Current Rating |
Standard |
Knife blade contact fuses | 690VAC | 16 to 800A | DIN 43620 |
Fuses with bolted contact | 690VAC | 16 to 800A | DIN43653 |
Cylindrical fuses | 500 to 690VAC | 6 to 100A | N/A |
Size |
Voltage rating |
5 x 20 mm | AC 250 V |
6.35 x 32 mm | AC 500 - 1000 V |
10 x 38 mm | AC 600 - 1000 V |
14 x 51 mm | AC 500/600V - 690/700 V |
22 x 58 mm | AC 500/600 V - 690/700 V |
27 x 60 mm | AC 660 V - 1000 V |
Standards: | IEC 60269-4 and -1; DIN VDE 0636-23;UL 248-13 |